Application Note
Using ELPRO 805U Modems with Profibus
©ELPRO Technologies Pty Ltd August 2001
Page 6 of 7 APP_805U_PROFIBUS_R1-0.Doc
Configuration for 93,750 baud operation
805U Modem Configuration
The following table lists the configuration settings for the 805U. From Factory defaults,
the followng settings are required.
Radio Baud Rate: 76,800 baud.
Serial Baud Rate : 93,750 baud (Note: requires firmware version 1.72 or later).
Character Format: 8 data, even parity, 1 stop.
Error Checking : Enabled
Flow Control: RS-485 Mode
Note: PC Serial ports cannot be set to the 93,750 baud rate, so the final command should
set the baud rate and write the parameters to memory. The following listing demonstrates
this. After the final command “atc13&w” the terminal will be unable to communicate
with the modem, as the modem will be set to 93,750 baud.
Profibus Network Configuration
The Profibus network is configured with a T_Slot time of 4000, T_Set value of 494 bits,
and a Max_T_Sdr time of 1023 bits. The Profibus Data rate is set to 93,750 baud. The
following diagrams show the screens required for configuration of a Siemens S7 PLC
using STEP7 configuration software.
OK
ati
905U-D/805U V1.72
OK
at&f
OK
atb2&b14&e1&w
OK
at&v
B2 C4 E1 Q0 V1 X0 &B14 &C1 &D0 &E1 &G0 &K4 &L1 &M0 &N1 &S100 &U1 \T0
S0:1 S1:50 S2:43 S3:13 S4:10 S5:8 S6:0 S7:5 S8:0 S9:0 S10:1 S11:0 S12:1
S13:3 S14:255 S15:0 S16:0 S17:0 S18:0 S19:0 S20:100
&Z0= &Z1=
&Z2= &Z3=
OK
atc13&w
Vue de la page 63