Application Note 105U-G-PR2 Profibus Master
Issue 1.2 – May 2005
©ELPRO Technologies Pty Ltd
Page 10 of 13
app_105U-G_PR2_1.2.doc
Once the Digital inputs are turned on the register locations 4306 & 4307 are filled with FFFF
indicating that the inputs are on and will be written to the Fieldbus I/O location configured, which
in turn turns the Digital outputs on the ET200S on.
The Disable Read Area and Disable Write
Area are used when diagnostics are needed
for configurations over the radio network.
If you can read values from the slave device but are not
able to get them sent to the correct destination or you
believe values are incorrect you can select Disable Read
Area. This will stop the Slave device overwriting values
from the Fieldbus Interface into the I/O database so you
can then double click on a register location that is being
mapped over the radio network enter in a value and check
it at the destination module to confirm correct location
and value.
Once this has been confirmed ensure that the Disable
Read Area has been deselected.
If you want to do local diagnostics to view values coming in from the radio network without
sending value to the Profibus Slave device and you can not disconnect the Profibus cable due to
creating a possible Bus Failure for other devices on the network you can select Disable Write
Area. This will stop any values being written to the Fieldbus and onto the Profibus Slave device.
Once this testing is completed ensure that the Disable Write Area has been deselected.