GreenMatic I Lundeager 24 I 2791 Dragør I Tel. 7020 4840 I Fax 7020 4847 I www.greenmatic.dk
Specifications
0508
Power Supply
9 – 30VDC / 12 – 24VAC
Battery charging circuit included for 12V back-up battery,
max charge current regulated to 0.7A (>12V supply)
Normal current drain
Modbus / DF1 version 12V 150mA; 24V 90mA
Profibus / Ethernet 12V 270mA; 24V 170mA
Add 5mA per active I/O
Current drain during radio transmission - add to above
12V 350mA; 24V 200mA
General
Modbus/DF1 version
-20 to 60 degC, 0 - 99 %RH
Profibus / Ethernet / DeviceNet / Modbus Plus
0 to 60 degC, 0 - 95 %RH
EMC Compliant EN55022, EN50082-1, FCC Part 15
Housing - extruded aluminium case 130 x 185 x 60 mm,
DIN rail mounting, removable terminal blocks for ease of
module replacement, terminals suitable for 2.5sqmm wire
LED indication for processor OK, radio TX and RX, serial
TX and RX, active status.
I/O Capacity
Modbus / DF1 4300 I/O points (analog plus discrete)
Profibus 416 I/O bytes
up to 1952 discrete inputs / 1952 discrete outputs
or up to 122 analog in / 122 analog out
Ethernet 2048 bytes input and 2048 bytes output
up to 4300 discrete I/O points
or up to 1024 analog in / 1024 analog out
DeviceNet 512 bytes input and 512 bytes output
up to 4300 discrete I/O or
up to 256 analog in / 256 analog out
Modbus Plus 2048 bytes input and 2048 bytes output
up to 4300 discrete I/O or
up to 1024 analog in / 1024 analog out
Register size 16 bit
Number of remote 105U addresses 500
Radio Transceiver
Single channel, synthesised, direct frequency modulation.
Frequency 405-490 MHz, 12.5KHz channels, 10-500mW, 5W
220-230 MHz, 25KHz channels, 5W
869.525 MHz, 250KHz channel, 500mW
Approved to EN 300 220, AS4268.2, RFS29
Expected line-of-sight range, with unity gain antennas
10mW - 2km; 500mW - 5km(869Mz) / 10km (400MHz);
5W - 40km (220MHz) / 30km (400MHz)
Range may be extended by up to four intermediate
repeaters.
Radio Transmission
Radio communications can be configured for combination
of event reporting (change-of-value), update time, read/
write blocks and poll response.
Radio message includes system addressing, unit
addressing, error-checking and configurable security
encryption.
Communication control includes message
acknowledgments and up to four re-transmissions.
Peer to peer addressing. Messages may be routed thru
four intermediate repeater addresses.
Fail-to-transmit and fail-to-receive alarms configurable
Modbus Specification
Modbus RTU (binary), master / slave configurable.
RS232 or RS485, 300 - 19200 bits/sec.
DF1 Specification
Allen-Bradley DF1 full-duplex.
RS232 only, 300 - 19200 bits/sec.
Profibus
Profibus-DP Slave functionality according to EN 50170.
RS-485 optically isolated with on-board DC/DC converter,
automatic baudrate detection (9600 bit/s - 12 Mbit/s)
Ethernet
10/100 Mbit/s, RJ45 transformer isolated interface
Modbus/TCP class 0, class 1 and partially class 2 slave
EtherNet/IP level 2 I/O Server
Embedded Web system (Dynamic HTTP), on-board file
system (1.4MB flash disc), user downloadable web pages
through FTP server, Email functionality (SMTP)
DeviceNet
DeviceNet 2.0 Slave, optically isolated RS422 with
selectable baudrate 125, 250 and 500 Kbit/sec.
Modbus Plus
Modbus Plus Slave, optically isolated RS485 with standard
baudrate of 1 Mbit/sec, global data base transactions with
routing for up to six networks.
On-board I/O
Eight discrete I/O, individually configurable as input or
output. Inputs suitable for voltage free contacts.
Outputs are FET, 30VDC 500mA.
Configuration & Diagnostics
Configuration via free Windows software
Diagnostics include on-line read/write of I/O registers,
radio signal strength values from remote units, and off-line
testing of data bus protocol.
9/12 Billabong St, Stafford, Qld, 4053 Australia
Telephone: +61 7 3352 4533
Fax: +61 7 3352 4577
Internet: www.elprotech.com