455U-D_Radio-Modem_Profi bus
0508
Application Note 455U-D Radio Modem with Profibus
Issue 1.0 – December/06
©ELPRO Technologies Pty Ltd
Page 6 of 6
app_455UD_PROFIBUS_1.0.doc
When testing ensure that the Signal levels are within an acceptable range so that the signals are not
too strong or too weak giving false indications.
Signal Strength levels can be checked whilst testing via the configuration port and using a terminal
package. Serial settings are 9600, 8, N, 1.
Enter in command at&t5 (RSSI Measurement) and monitor the rolling average Signal Detect
specifications for the 455U-D are -120 to -60dBm.
Amendment Register:
Issue No. Date Details of Amendment
1.0 30-11-06 Initial Issue
Adjust Parameters to
values as shown.
Download new
settings to PLC and
restart with modems
connected.
Ensure Cabling
between Profibus
Devices and 455U-D
modems is correct as
per above.
at&t5
Signal Strength Display
This Sample Rolling Average
Min Max Min Max
-109 dBm -099 dBm -113 dBm -075 dBm
RSSI Level
Noise Floor