Application Note 105/905U-G-ET1 Modbus TCP
Issue 1.2 – Apr 2006
©ELPRO Technologies Pty Ltd
Page 5 of 12
app_905U-G_ModbusTCP_1.2.doc
Each Tag needs to have
Name – Tag name
Modbus address – Standard Modbus
command & address i.e 1X, 3X, 4X or 0X
Description - Description of what the I/O is.
Data type – Select Word as all Gateway
registers are 16 bit
Client Access – Read only for inputs or
Read/Write for Outputs.
Scan Rate – Default 100 mSec.
You can also setup Scaling on
each of the Tags if you wish.
105/905U-G I/O registers are
16 bit (0 – 65535) and a
typical range for an analog
value from a field station is
4mA = 16384 decimal
20mA = 49152 decimal
This is shown here as being a
linear scale of 0 to 100 % is
equal to decimal value 16384
to 49152
For Firmware versions 1.76 and above Scaling of the I/O registers can be applied in the
E-series configuration software for all read and write commands.