Application Note 105/905U-G-ET1 Modbus TCP
Issue 1.2 – Apr 2006
©ELPRO Technologies Pty Ltd
Page 4 of 12
app_905U-G_ModbusTCP_1.2.doc
Create a new Channel and add the
following
Name – Any name you want
Model – Select Modbus
IP address – Must be the same as the
one configured in the 105/905U-G-
ET1
Timeout times -Default. Connect
timeout = 3, Request Timeout =
1000, Fail after = 3.
TCP/IP port - 502.
When this is done you can setup appropriate tags for the I/O.
In this example I have setup 4 Modbus Read Word Tags starting at Modbus address 30001
tags and 1 Modbus Write word Tag at address 41025.
The Modbus Command is made up of a Command and a Modbus Address.
Modbus commands are 0X = Write Bit, 1X = Read Bit, 3X = Read Word, 4X = Write Word
So 30001 will Read Word at Modbus location 1 or 41025 will Write Word to Modbus
Location 1025.
For Further Information on addressing refer to ELPRO 105/905U-G Manual for
Modbus TCP Addressing Ranges