GreenMatic I Lundeager 24 I 2791 Dragør I Tel. 7020 4840 I Fax 7020 4847 I www.greenmatic.dk
Specifi cations
0508
Power Supply
• 10 - 30 VDC or 10 - 24 VAC supply
• Normal current drain 70mA/12VDC or 50mA/24VDC
• Current when transmitting 350mA/12V or 250mA/ 24V
Low power mode current drain 20mA/12VDC or 15mA/24VDC
General
• Environmental -40 to +140 degF (-40 to 70 degC)
• EMC Compliant FCC Part 15 Class A
• Housing, extruded aluminum case 4.5”x 7.3”x 1.2”(114 x 185 x
30mm) DIN rail mounting, removable terminal blocks for
ease of module replacement, terminals suitable for 12 gauge
(2.5sqmm) conductors.
LED indication for unit OK, radio TX and RX, serial TX and RX,
DCD (comms OK).
Serial Port
• Standard data rates 1200 to 115200 baud.
• RS232 and RS485 standard interface connections provided,
each connected to the same serial port. Serial interfaces are
asynchronous non-return-zero (NRZ) format.
• Characters supported 7 or 8 data bits, even/odd/no parity,
1 or 2 stop bits
• RS232 connection provides full duplex operation as a DCE
device with RTS/CTS hardware handshaking- standard D9
connector.
• RS485 connection provides half duplex operation for twisted-
pair multidrop networks.
• Input and output buers 2Kbyte
Radio Transceiver
Frequency Hopping Spread Spectrum Transceiver
Frequency - USA/Canada 902 - 928 MHz
- Australia 915 - 928 MHz
- NZ 921 - 928MHz
• Hop Sequence - 16 x 50
Transmit Power 1W
• RSSI –120 to -60 dBm
• Expected line-of-sight range, depending on local conditions
- USA/Canada 20+ miles
- Australia/NZ 20+ km
• RF Data Transmission Rate - 19200 baud, 57600 baud, 115200
baud (selectable)
• Range may be extended by: - up to ve intermediate repeaters
in controlled mode - unlimited repeaters in transparent mode
• Conforms to FCC Part 15 Class A and FCC Part 15.247
• Antenna connection is SMA coaxial
Data Transmission
Transparent mode: Data is transmitted with a system and
group address. Data transmission begins as serial data is
received – maximum packet size is 530 bytes. All modules,
with correct system address, which receive the data packets,
outputs the data - error checking is optional.
• Controlled mode: Data is transmitted in packets with a
system address, source address, destination address, up to
ve intermediate repeater addresses, and a 16 bit CRC error
check. If the packet is received with a correct error check,
only the destination module will output the data and will
also return an ACK transmission. If the source module does
not receive the ACK, it will retry a further four times. DCD
provides communications status.
• Auto-connect and dial-up-control modes are available.
• CTS/RTS ow control provided based on input buer
availability.
Conguration and Diagnostics
AT commands. Radio noise, signal strength and bit error
rate (BER) diagnostics included. Radio signal strength value
available on-line to host device.