Elpro Technologies 105U-G Spécifications Page 34

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 66
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 33
Application Note 105/905U-G-ET1 Modbus TCP
Issue 1.2 – Apr 2006
©ELPRO Technologies Pty Ltd
Page 8 of 12
app_905U-G_ModbusTCP_1.2.doc
Press “Connect” button and you should get a Green Connected indication. Then tick
“Continuous and press “Read” button.
The E-series configuration will now be continuously scanning the I/O Database in the 105/905U-
G.
Back in the 105/905U-G Configuration section we configured Registers 1,2,3,4 to be written
across to the Fieldbus location 1,2,3,4 (Modbus Tag Commands 30001,30002, 30003, 30004)
and also Fieldbus location 1025 (Modbus Tag Command 41025) is being read into Reg 10.
We can edit the registers in the I/O Register Selection Window by double clicking on the
register which will open a modufy box like this
From here we can enter a value into the register in
the available formats i.e Hex, Decimal or Discrete.
Then press “OK” and you should notice the Tag
Value change on the OPC Server screen
Vue de la page 33
1 2 ... 29 30 31 32 33 34 35 36 37 38 39 ... 65 66

Commentaires sur ces manuels

Pas de commentaire